Product Specifications
VoltModelMeasurement RangeResolutionAccuracy
Vrms (AC + DC)1 V to 1000 V phase to neutral0.01 V±0.1% of nominal voltage1
Vpk1 Vpk to 1400 Vpk1 V5% of nominal voltage
Voltage Crest Factor (CF)1.0 > 2.80.01±5%
Vrms½
0.1 V±0.2% of nominal voltage
Vfund
0.1 V±0.1% of nominal voltage
Amps (accuracy excluding clamp accuracy)
Amps (AC + DC)i430-Flex 1x 5 A to 6000 A1 A±0.5% ±5 counts
i430-Flex 10x0.5 A to 600 A0.1 A±0.5% ±5 counts
1mV/A 1x5 A to 2000 A1A±0.5% ±5 counts
1mV/A 10x0.5 A A to 200 A (AC only)0.1 A±0.5% ±5 counts
Apki430-Flex8400 Apk1 Arms±5%
1mV/A5500 Apk1 Arms±5%
A Crest Factor (CF)1 to 100.01±5%
Amps½i430-Flex 1x5 A to 6000 A1 A±1% ±10 counts
i430-Flex 10x0.5 A to 600 A0.1 A±1% ±10 counts
1mV/A 1x5 A to 2000 A1 A±1% ±10 counts
1mV/A 10x0.5 A A to 200 A (AC only)0.1 A±1% ±10 counts
Afundi430-Flex 1x5 A to 6000 A1 A±0.5% ±5 counts
i430-Flex 10x0.5 A to 600 A0.1 A±0.5% ±5 counts
1mV/A 1x5 A to 2000 A1 A±0.5% ±5 counts
1mV/A 10x0.5 A A to 200 A (AC only)0.1 A±0.5% ±5 counts
Hz
Fluke 434 @ 50 Hz Nominal42.50 Hz to 57.50 Hz0.01 Hz±0.01 Hz
Fluke 434 @ 60 Hz Nominal51.00 Hz to 69.00 Hz0.01 Hz±0.01 Hz
Power
Watts (VA, var)i430-Flexmax 6000 MW0.1 W to 1 MW±1% ±10 counts
1 mV/Amax 2000 MW0.1 W to 1 MW±1% ±10 counts
Power Factor (Cos j/DPF)0 to 10.001±0.1% @ nominal load conditions
Energy
kWh (kVAh, kvarh)i430-Flex 10xDepends on clamp scaling and V nominal±1% ±10 counts
Energy Lossi430-Flex 10xDepends on clamp scaling and V nominal±1% ±10 counts Excluding line resistance accuracy
Harmonics
Harmonic Order (n)DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
Inter-Harmonic Order (n)OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
Volts %f0.0% to 100%0.1%±0.1% ±n x 0.1%
r0.0% to 100%0.1%±0.1% ±n x 0.4%
Absolute0.0 to 1000 V0.1 V±5%1
THD0.0% to 100%0.1%±2.5%
Amps %f0.0% to 100%0.1%±0.1% ±n x 0.1%
r0.0% to 100%0.1%±0.1% ±n x 0.4%
Absolute0.0 to 600 A0.1 A±5% ±5 counts
THD0.0% to 100%0.1%±2.5%
Watts %f or r0.0% to 100%0.1%±n x 2%
AbsoluteDepends on clamp scaling and V nominal±5% ±n x 2% ±10 counts
THD0.0% to 100%0.1%±5%
Phase Angle-360° to +0°±n x 1°
Flicker
Plt, Pst, Pst (1 min) Pinst0.00 to 20.000.01±5%
Unbalance
Volts %0.0% to 20.0%0.1%±0.1%
Amps %0.0% to 20.0%0.1%±1%
Mains Signaling
Threshold LevelsThreshold, limits and signaling duration is programable for two signaling frequencies
Signaling Frequency60 Hz to 3000 Hz0.1 Hz
Relative V %0% to 100%0.10%±0.4%
Absolute V3s (3 second avg.)0.0 V to 1000 V0.1 V±5% of nominal voltage
General Specifications
CaseDesign Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
DisplayBrightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
Memory8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32 GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size)
Real-Time ClockTime and date stamp for Trend mode, Transient display, System Monitor and event capture
Environmental
Operating Temperature0°C ~ +40°C; +40°C ~ +50°C excl. battery
Storage Temperature-20°C ~ +60°C
Humidity+10°C ~ +30°C: 95% RH non-condensing
+30°C ~ +40°C: 75% RH non-condensing
+40°C ~ +50°C: 45% RH non-condensing
Maximum Operating AltitudeUp to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
Maximum storage altitude 12 km (40,000 ft)
Electro-Magnetic-Compatibility (EMC)EN 61326 (2005-12) for emission and immunity
InterfacesMini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery
WarrantyThree years (parts and labor) on main instrument, one year on accessories
View full family specifications »
1. ±5% if ≥ 1% of nominal voltage ±0.05% of nominal voltage if < 1% of nominal voltage
2. 50Hz/60Hz nominal frequency according to IEC 61000-4-30
3. 400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode
4. For nominal voltage 50 V to 500 V